ANALISIS PENGARUH MAINTENANCE INSTALASI LOW VOLTAGE SWITCHGEAR TERHADAP KUALITAS LISTRIK PADA JARINGAN DISTRIBUSI TEGANGAN RENDAH (LVMDP)

ADDAILAMI, RIZKI BARKAH (2023) ANALISIS PENGARUH MAINTENANCE INSTALASI LOW VOLTAGE SWITCHGEAR TERHADAP KUALITAS LISTRIK PADA JARINGAN DISTRIBUSI TEGANGAN RENDAH (LVMDP). S1 thesis, Universitas Mercu Buana Bekasi.

[img]
Preview
Text
41418310015 - Rizki Barkah Addailami - 01 Cover.pdf

Download (623kB) | Preview
[img]
Preview
Text
41418310015 - Rizki Barkah Addailami - 02 Abstrak.pdf

Download (106kB) | Preview
[img] Text
41418310015 - Rizki Barkah Addailami - 03 Bab I.pdf
Restricted to Registered users only

Download (210kB)
[img] Text
41418310015 - Rizki Barkah Addailami - 04 Bab II.pdf
Restricted to Registered users only

Download (736kB)
[img] Text
41418310015 - Rizki Barkah Addailami - 05 Bab III.pdf
Restricted to Registered users only

Download (1MB)
[img] Text
41418310015 - Rizki Barkah Addailami - 06 Bab IV.pdf
Restricted to Registered users only

Download (261kB)
[img] Text
41418310015 - Rizki Barkah Addailami - 07 Bab V.pdf
Restricted to Registered users only

Download (74kB)
[img] Text
41418310015 - Rizki Barkah Addailami - 08 Daftar Pustaka.pdf
Restricted to Registered users only

Download (247kB)
[img] Text
41418310015 - Rizki Barkah Addailami - 09 Lampiran.pdf
Restricted to Registered users only

Download (332kB)

Abstract

ABSTRAK Keandalan dan Kemampuan suatu Sistem Tenaga Listrik dalam melayani mesin-mesin atau peralatan yang menggunakan tenaga listrik dipengaruhi salah satunya oleh kegiatan Maintenance. Maintenance Jaringan Distribusi Tegangan Rendah merupakan kegitan pemeliharaan instalasi perangkat jaringan distribusi dari mulai MVMDP, Trafo Stepdown sampai LVMDP-SDP. Maintenance Instalasi Jaringan Distribusi Tegangan Rendah dilaksanakan untuk memastikan atau menjaga perangkat Instalasi dalam keadaan baik atau layak, parametermya dapat dilihat dari nilai resistansi penghantar dan kontak hubungnya, dengan Instalasi perangkat yang baik, maka kinerja pada pemutus arus pada saat terjadi gangguan akan tepat. Hasil uji tes pada saat maintenance akan menunjukan besaran nilai tahanan instalasi jaringan distribusi yaitu, nilai tahanan isolasi, nilai tahanan kontak, dan tahanan winding pada trafo. Nilai Uji Tes mengacu pada standar yang telah ditentukan. Standar IEC 60470 & JEC-181-1971 (batas waktu kontak circuit breaker), IEC 60076- 1 Tahun 2011 (tahanan insulasi), IEEE C57.125 (tahanan insulasi trafo). Maintenance Instalasi Jaringan Tegangan Rendah mencakup; Kondisi ruangan peralatan, Kondisi perangkat/switchgear (panel MVMDP, Trafo, Panel LVMDP) Kondisi circuit breaker, cable/busbar, jointing cable/busbar, trafo, Fungsional trip circuit breaker, MCCB, MCB. Terdapat perubahan cukup signifikan pada nilai uji tes setelah dilakukannya maintenance, Tahanan insulasi ; MVMDP Δ 11.1 GΩ, transformator step down Δ 42 MΩ, LVMDP Δ 24 MΩ. Tahanan kontak pada busbar/joint contact Δ 7.2 µΩ. Kata Kunci: Maintenace, Jaringan Tegangan Rendah, Tahanan Insulasi, Tahanan Kontak ABSTRACT The reliability and capability of an electric power system in servicing machines or equipment that uses electric power is influenced by activities Maintenance. Maintenance The Low Voltage Distribution Network is a maintenance activity for the installation of distribution network devices starting from MVMDP, transformers Step Down up to LVMDP-SDP. Maintenance of the Low Voltage Distribution Network Installation is carried out to ensure or maintain the installation equipment in good or proper condition, the parameters can be seen from the value of the resistance of the conductors and the contacts, with a good device installation, the performance of the circuit breaker in the event of a fault will be correct. The test results at the time maintenance will show the value of the installation resistance of the distribution network, namely the insulation resistance value, the contact resistance value, and the winding resistance of the transformer. Test Value The test refers to a predetermined standard. Standard IEC 60470 & JEC-181-1971 (contact time limit circuit breaker), IEC 60076- 1 Year 2011 (insulation resistance), IEEE C57.125 (transformer insulation resistance). Low Voltage Network Installation Maintenance includes; Condition of equipment room, Equipment/switchgear condition (MVMDP panel, transformer, LVMDP panel) Condition of circuit breaker, cable/busbar, jointing cable/busbar, transformer, Functional trip circuit breaker, MCCB, MCB. There is a significant change in the test value after maintenance, insulation resistance; MVMDP Δ 11.1 GΩ, step down transformer Δ 42 MΩ, LVMDP Δ 24 MΩ. Contact resistance at busbar/joint contact Δ 7.2 µΩ. Keywords: Maintenace, Low Voltage Network, Insulation Resistance, Contact Resistance

Item Type: Thesis (S1)
Call Number CD: FT/ELK 23 004
NIM/NIDN Creators: 41418310015
Uncontrolled Keywords: Maintenace, Jaringan Tegangan Rendah, Tahanan Insulasi, Tahanan Kontak
Subjects: 600 Technology/Teknologi > 620 Engineering and Applied Operations/Ilmu Teknik dan operasi Terapan > 621 Applied Physics/Fisika terapan > 621.3 Electrical Engineering, Lighting, Superconductivity, Magnetic Engineering, Applied Optics, Paraphotic Technology, Electronics Communications Engineering, Computers/Teknik Elektro, Pencahayaan, Superkonduktivitas, Teknik Magnetik, Optik Terapan, Tekn
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: siti maisyaroh
Date Deposited: 17 May 2023 07:18
Last Modified: 17 May 2023 07:18
URI: http://repository.mercubuana.ac.id/id/eprint/77273

Actions (login required)

View Item View Item