YUSUF, MUHAMMAD (2020) RANCANG BANGUN SISTEM KENDALI SUHU DAN KELEMBABAN KUBIKEL 20 KV DENGAN KONTROL PID BERBASIS LABVIEW. S1 thesis, Universitas Mercu Buana Bekasi.
|
Text
1. Halaman judul.pdf Download (40kB) | Preview |
|
|
Text
2. Halaman pernyataan.pdf Download (122kB) | Preview |
|
|
Text
3. Halaman pengesahan.pdf Download (116kB) | Preview |
|
|
Text
4. Kata pengantar.pdf Download (23kB) | Preview |
|
|
Text
5. Abstrak.pdf Download (28kB) | Preview |
|
|
Text
6. Daftar isi.pdf Download (26kB) | Preview |
|
|
Text
7. Daftar gambar.pdf Download (26kB) | Preview |
|
|
Text
8. Daftar tabel.pdf Download (22kB) | Preview |
|
Text
9. Bab 1.pdf Restricted to Registered users only Download (167kB) |
||
Text
10. Bab 2.pdf Restricted to Registered users only Download (406kB) |
||
Text
11. Bab 3.pdf Restricted to Registered users only Download (412kB) |
||
Text
12. Bab 4.pdf Restricted to Registered users only Download (518kB) |
||
Text
13. Bab 5.pdf Restricted to Registered users only Download (25kB) |
||
Text
14. Daftar pustaka.pdf Restricted to Registered users only Download (77kB) |
Abstract
ABSTRAK Setiap kubikel selalu dilengkapi dengan sarana penunjang berupa heater, yaitu alat untuk memanaskan udara didalam kubikel agar terhindar dari kelembaban, namun heater tersebut pada kondisi suhu beranjak naik akibat beban atau arus yang besar tidak bisa menolong, justru panas yang dikeluarkan oleh heater tersebut menyebabkan kenaikan tingkat uap air jenuh udara yang ada didalam kubikel tersebut. Kondisi ini akan meningkatkan nilai kelembaban yang bisa menyebabkan terjadinya korona dan kegagalan isolasi udara. Berdasarkan hal tersebut, pada penelitian ini dibuat suatu prototype rancang bangun untuk menstabilkan kondisi suhu dan kelembaban kubikel 20 kV dengan sistem kontrol Proposional Integral Deravatif (PID) berbasis LabVIEW. Dengan menggunakan sistem kontrol PID sebagai pengendali suhu pada lampu pijar sebagai plant sehingga terjadi kestabilan suhu yang terjaga dengan mengatur nilai konstanta proposional (Kp), konstanta integral (Ki), dan konstanta derivatif (Kd) yang sesuai dan dimonitoring pada LabVIEW. Berdasarkan hasil perancangan, pengujian dan analisa yang dilakukan, maka penulis dapat menarik kesimpulan bahwa dengan menggunakan metode trial and error pada penelitian ini yaitu lampu pijar sebagai plant dapat menstabilkan suhu dan kelembaban dengan nilai Kp= 1, Ki= 0,1, dan Kd= 0,05 pada setpoint 40°C diperoleh parameter rise time = 188s, peak time = 216s, settling time = 288s, dan error steady state = 0,30%. Pada setpoint 43°C diperoleh parameter rise time = 272s, peak time = 311s, settling time = 377s, dan error steady state = 0,60%. Pada setpoint 45°C diperoleh parameter rise time = 338s, peak time = 380s, settling time = 448s, dan error steady state = 0,93%. Kata Kunci : Kubikel 20 kV, PID, Trial and Error ABSTRACT Each cubicle is always equipped with supporting facilities such as a heater, which is a tool to heat the air inside the cubicle to avoid moisture, but the heater is in a condition of rising temperature due to heavy loads or currents can not help, instead the heat released by the heater causes an increase in the level saturated air vapor in the cubicle. This condition will increase the value of humidity which can cause corona and failure of air insulation. Based on this, in this study a prototype design was made to stabilize the temperature and humidity conditions of the 20 kV cubicle with a LabVIEWbased Proposional Integral Deravative (PID) control system. By using the PID control system as a temperature controller on incandescent lamps as a plant so that temperature stability is maintained by adjusting the proportional constants (Kp), integral constants (Ki), and derivative constants (Kd) that are appropriate and monitored on LabVIEW. Based on the results of the design, testing and analysis carried out, the authors can draw the conclusion that by using the trial and error method in this study that incandescent lamps as a plant can stabilize temperature and humidity with values of Kp = 1, Ki = 0.1, and Kd = 0.05 at 40 ° C setpoint obtained the rise time = 188s, peak time = 216s, settling time = 288s, and steady state error = 0,30%. At setpoint 43 ° C, the rise time parameter = 272s, peak time = 311s, settling time = 377s, and steady state error = 0,60%. At the 45 ° C setpoint, the rise time parameter = 338s, peak time = 380s, settling time = 448s, and steady state error = 0,93%. Keywords: Cubicle 20 kV, PID, Trial and Error
Item Type: | Thesis (S1) |
---|---|
Call Number CD: | FE/ELK 20 017 |
NIM/NIDN Creators: | 41416310059 |
Uncontrolled Keywords: | Kata Kunci : Kubikel 20 kV, PID, Trial and Error |
Subjects: | 600 Technology/Teknologi > 620 Engineering and Applied Operations/Ilmu Teknik dan operasi Terapan > 621 Applied Physics/Fisika terapan > 621.3 Electrical Engineering, Lighting, Superconductivity, Magnetic Engineering, Applied Optics, Paraphotic Technology, Electronics Communications Engineering, Computers/Teknik Elektro, Pencahayaan, Superkonduktivitas, Teknik Magnetik, Optik Terapan, Tekn |
Divisions: | Fakultas Teknik > Teknik Elektro |
Depositing User: | siti maisyaroh |
Date Deposited: | 15 Jun 2022 04:42 |
Last Modified: | 15 Jun 2022 04:42 |
URI: | http://repository.mercubuana.ac.id/id/eprint/63378 |
Actions (login required)
View Item |