EVALUASI EFEKTIVITAS KINERJA SEWAGE TREATMENT PLANT PADA GEDUNG GKM GREEN TOWER

RENDRA, ALDERA AJI MAHA (2023) EVALUASI EFEKTIVITAS KINERJA SEWAGE TREATMENT PLANT PADA GEDUNG GKM GREEN TOWER. S1 thesis, Universitas Mercu Buana Jakarta.

[img]
Preview
Text (HAL COVER)
1. Hal Cover.pdf

Download (331kB) | Preview
[img]
Preview
Text (ABSTRAK)
2. Abstrak.pdf

Download (81kB) | Preview
[img] Text (BAB I)
3. BAB I.pdf
Restricted to Registered users only

Download (76kB)
[img] Text (BAB II)
4. BAB II.pdf
Restricted to Registered users only

Download (331kB)
[img] Text (BAB III)
5. BAB III.pdf
Restricted to Registered users only

Download (37kB)
[img] Text (BAB IV)
6. BAB IV.pdf
Restricted to Registered users only

Download (1MB)
[img] Text (BAB V)
7. BAB V.pdf
Restricted to Registered users only

Download (23kB)
[img] Text (DAFTAR PUSTAKA)
8. Daftar Pustaka.pdf
Restricted to Registered users only

Download (135kB)
[img] Text (LAMPIRAN)
9. Lampiran.pdf
Restricted to Registered users only

Download (147kB)

Abstract

Waste water or waste water is the remaining water that is disposed of originating from households, industries, offices, and other public places. Sewage Treatment Plant (STP) is a process of reuse of wastewater, a process to remove contaminants from wastewater. This study evaluates the Sewage Treatment Plant system in the GKM Green Tower Building. The purpose of this study is to analyze the performance of the Sewage Treatment Plant (STP) in the GKM Green Tower building and to determine the effectiveness of the performance of the Sewage Treatment Plant (STP) in the GKM Green Tower building. The parameters used in this study were pH (acidity), COD, BOD, TSS, oil and grease, Total Coliform, Ammonia which complies with Domestic Wastewater Quality Standards Based on the Regulation of the Minister of Environment and Forestry of the Republic of Indonesia Number: P.68/ Menlhk-Setjen/2016. Recycle water in the GKM Green Tower building is used for flushing closed, urinal, and is also used to water plants in the building. It was found that the results of clean wastewater management in the GKM Green Tower building still look cloudy and smelly. Based on the results of domestic wastewater monitoring tests at GKM Green Tower in August / prior to analysis, there were several parameters that exceeded the quality standards, namely TSS and Total Coliform. The Maintenance carried out so far on the Sewage Treatment Plant (STP) system in the GKM Green Tower Building is still not good, so this is the cause of the ineffectiveness of the wastewater that has been managed so far. The results of the second test conducted in November showed a decrease in the number among the TSS parameters, namely as many as 13, so that it became 23. In addition, the Total Coliform was 38,000, so that the Total coliform became 3,000. So that it is in accordance with the quality standards set government ministry of environment. Keywords: Wastewater, Sewage Treatment Plant (STP), GKM Green Tower Building, Domestic wastewater quality standard

Item Type: Thesis (S1)
Call Number CD: FT/MSN. 23 011
Call Number: ST/13/23/021
NIM/NIDN Creators: 41318110054
Uncontrolled Keywords: Wastewater, Sewage Treatment Plant (STP), GKM Green Tower Building, Domestic wastewater quality standard
Subjects: 600 Technology/Teknologi > 620 Engineering and Applied Operations/Ilmu Teknik dan operasi Terapan
600 Technology/Teknologi > 620 Engineering and Applied Operations/Ilmu Teknik dan operasi Terapan > 621 Applied Physics/Fisika terapan
600 Technology/Teknologi > 620 Engineering and Applied Operations/Ilmu Teknik dan operasi Terapan > 621 Applied Physics/Fisika terapan > 621.8 Machine Engineering, Machinery/Teknik Mesin
Divisions: Fakultas Teknik > Teknik Mesin
Depositing User: ADELINA HASNA SETIAWATI
Date Deposited: 31 Mar 2023 03:00
Last Modified: 31 Mar 2023 03:00
URI: http://repository.mercubuana.ac.id/id/eprint/75744

Actions (login required)

View Item View Item